Remote Legionella temperature monitoring: how it works

How remote Legionella temperature monitoring works: what gets measured, how readings reach a portal, what it replaces, what drives the cost and what to ask a supplier.

By Alessio Grespi, Founder & CEO

Remote Legionella temperature monitoring swaps the monthly round with a thermometer for sensors that take readings on their own and send them to a portal. The checks themselves do not change. What changes is who takes them, how often, and how quickly a problem is noticed.

This post explains what gets measured, how the readings travel, what the sensors do and do not replace, and what to ask before you buy.

What gets monitored

Legionella bacteria multiply in lukewarm water, so temperature is the main control in most buildings. Keep hot water hot, keep cold water cold, and prove it. The Health and Safety Executive (HSE) sets out the targets in its guidance on hot and cold water systems and in HSG274 Part 2.

WhereTargetUsual manual check
Hot water storage (calorifier)Stored at 60°C or aboveFlow and return temperatures
Hot outlets50°C within one minute of running (55°C in healthcare)Sentinel outlets monthly
Cold outletsBelow 20°C after running for two minutesSentinel outlets monthly
Cold water storage tanksKept cold and inspectedPeriodic inspection

Sentinel outlets are the taps nearest to and furthest from the tank or cylinder. If those two are in range, the pipework between them probably is too. HSE's checklist of things to consider lists the routine checks.

A remote system puts a temperature probe at each of these points. Your risk assessment decides which points matter in your building.

How the readings travel

  1. Probe. A temperature probe is fixed to the pipe, outlet supply or tank. It needs no plumbing work in most cases.
  2. Node. A small battery-powered unit reads the probe at set intervals, typically every few minutes.
  3. Connection. The node sends readings over a low-power radio to a gateway on site, or directly over the mobile network or Wi-Fi. The right choice depends on the building.
  4. Cloud. Readings are stored with a timestamp and the identity of the device that took them.
  5. Portal and alerts. You see every point on a dashboard. If a reading stays out of range, the right person gets an alert.
  6. Reports. The record is ready for an audit without anyone typing up a logbook.

What it replaces, and what it does not

Sensors take over the routine temperature readings and the record keeping that goes with them. They also catch things a monthly visit misses, such as a calorifier that drops overnight or a cold pipe that warms up every afternoon.

They do not replace the rest of a water hygiene regime.

  • Risk assessment. Still required, and still reviewed when the system or its use changes.
  • Flushing little-used outlets. A sensor can show that an outlet is not being used, because the pipe temperature shifts each time water moves through it. Someone still has to run it.
  • Sampling and inspection. Water samples, tank inspections and valve servicing still need a person on site.
  • Judgement. Someone competent has to decide what to do when a reading is wrong.

One point to be clear on: a probe on a pipe measures continuously, while the manual check measures water at a running tap. Agree with your responsible person or water hygiene contractor how the sensor readings map onto your written scheme.

What drives the cost

Pricing varies by supplier, but the same five things move it.

  • Number of monitored points. The biggest factor. Most suppliers charge per point per month.
  • Connectivity per site. One gateway can serve a whole building. Scattered small sites may suit nodes that connect directly.
  • Installation. Access, working at height and out-of-hours rules affect install time more than the hardware does.
  • Contract length. Longer terms usually lower the monthly figure.
  • Hardware model. Some suppliers sell the devices upfront. Others fold them into the subscription.

Set the cost against what it replaces: engineer hours, travel between sites, and the time spent turning paper readings into records.

Questions to ask a supplier

  1. Who owns the data, and can I export all of it at any time?
  2. Can a reading be edited after it is recorded? If so, by whom, and is that logged?
  3. What is the battery life at the reporting interval you are quoting?
  4. What happens when a node loses its connection? Are readings stored and sent later?
  5. How are alerts routed, and can I set the thresholds myself?
  6. What happens to the hardware and the data when the contract ends?
  7. Can the portal and reports carry my brand, if I am a contractor serving my own clients?

Frequently asked questions

Is remote temperature monitoring accepted for Legionella compliance? Yes. HSE's guidance says remote monitoring systems can be used to monitor hot and cold water systems, and that automated monitoring allows control failures to be detected early. The duty itself is unchanged: control the risk and keep records. Their strength is the pattern over time: how quickly an outlet heats up when it is run, whether a calorifier holds its temperature overnight, and when a cold pipe starts to drift. That change is what shows the control is working, more than any single reading. Whether they fully stand in for manual checks in your building is a decision for your risk assessment and responsible person.

How often do the sensors take a reading? It is configurable. Every few minutes is common, against once a month by hand.

Do the sensors need mains power or plumbing work? Usually neither. Nodes run on batteries and probes fix to the outside of the pipe.

Will it work in a basement plant room? Often, but not always on the first radio you try. A site survey settles it before install day.

Thinking about remote monitoring?

Paqett designs, deploys and runs water hygiene monitoring that contractors and facilities teams sell and use under their own brand. Talk to us about your sites.

Sources

Keep reading

Compliance· · 4 min read

Chain of custody for sensor data

Compliance data only counts if you can prove nobody changed it. What chain of custody means for sensor readings, where logbooks fail, and what to ask a vendor.

Water hygiene· · 5 min read

Manual vs automated Legionella monitoring

Monthly thermometer rounds or sensors? How manual and automated Legionella temperature monitoring compare on cost, coverage, records and risk, and when each makes sense.

Engineering· · 9 min read

Why per-device IoT pricing punishes fleets

Per-device and per-message IoT pricing scales with your success, not with what your fleet costs to host. A worked example at 1,000 and 50,000 devices, and the alternative.

Water hygiene· · 2 min read

Your rounds, plus the 29 days in between

A monthly temperature round is one reading per outlet. This is what the rest of the month looks like when a probe stays behind.

Engineering· · 5 min read

What chip for what kind of device

ESP32, Nordic nRF or RAK3172: which chip suits which kind of device, and what each one costs you.

Get new posts by email

One email when we publish. Nothing else.

Or talk to us about a deployment: water hygiene, white-label or built to spec.